Voltage drop calculator

Voltage drop in volts and percent for copper or aluminum wire on single-phase, three-phase and DC circuits.

Start from:

Voltage drop

7.92 volts (6.60%)

Voltage at the load
112.1 V
Wire resistance
1.98 Ω per 1,000 ft
Longest run within 3%
45 ft
Smallest size within 3% (drop only)
8 AWG
  • Over your 3% target: use a larger wire or a shorter run

Voltage drop is only one part of sizing wire

The wire must also be rated to carry the current (its ampacity, NEC Table 310.16), matched to the breaker, and suited to the insulation, temperature and installation. A size that keeps voltage drop low can still be too small to carry the load safely. Follow your local electrical code, and have a licensed electrician design and check the circuit.

Voltage drop formula

Current flowing through wire loses voltage to the wire's resistance. The calculator uses the resistance of the conductor from NEC Chapter 9, Table 8 (direct-current resistance at 75 °C).

  1. Single-phase and DC: VD = 2 × I × R × L ÷ 1,000 (the current goes out and back)
  2. Three-phase: VD = 1.732 × I × R × L ÷ 1,000
  3. Percent drop = VD ÷ source voltage × 100

I is the current in amps, R the resistance in ohms per 1,000 feet, and L the one-way length in feet.

Worked example

A 20 A load on 100 ft of 12 AWG copper at 120 V: R = 1.98 Ω per 1,000 ft, so VD = 2 × 20 × 1.98 × 100 ÷ 1,000 = 7.92 V, or 7.92 ÷ 120 = 6.6%. That's over the 3% guideline; 8 AWG copper would keep it within.

Results are estimates. Resistance rises with temperature, and for large conductors on AC the effective resistance in NEC Chapter 9, Table 9 is a little different.

Wire resistance and voltage drop chart

Resistance per 1,000 feet from NEC Chapter 9, Table 8 (stranded, 75 °C), and the longest one-way run that stays within 3% at 120 V and 15 A (voltage drop only).

SizeCopper Ω/1,000 ftAluminum Ω/1,000 ftMax run, copperMax run, aluminum
14 AWG3.145.1738 ft23 ft
12 AWG1.983.2560 ft36 ft
10 AWG1.242.0496 ft58 ft
8 AWG0.7781.28154 ft93 ft
6 AWG0.4910.808244 ft148 ft
4 AWG0.3080.508389 ft236 ft
3 AWG0.2450.403489 ft297 ft
2 AWG0.1940.319618 ft376 ft
1 AWG0.1540.253779 ft474 ft
1/0 AWG0.1220.201983 ft597 ft
2/0 AWG0.09670.1591,240 ft754 ft
3/0 AWG0.07660.1261,566 ft952 ft
4/0 AWG0.06080.11,973 ft1,199 ft
250 kcmil0.05150.08472,330 ft1,416 ft
300 kcmil0.04290.07072,797 ft1,697 ft
350 kcmil0.03670.06053,269 ft1,983 ft
400 kcmil0.03210.05293,738 ft2,268 ft
500 kcmil0.02580.04244,651 ft2,830 ft

Voltage drop questions

How much voltage drop is acceptable?

Informational notes to NEC 210.19(A) and 215.2(A) recommend sizing conductors so the drop is no more than 3% on a branch circuit and 5% for the feeder and branch circuit together. These are recommendations, not requirements, but following them keeps motors, lights and electronics working properly. Some equipment makers ask for less.

How do I calculate voltage drop?

Multiply 2 × current × resistance per 1,000 feet × one-way length, then divide by 1,000. For three-phase circuits use 1.732 instead of 2. The worked example above shows each step.

What is the three-phase voltage drop formula?

VD = 1.732 × I × R × L ÷ 1,000. For example, 100 A on 200 ft of 1/0 AWG aluminum at 480 V drops 6.96 V, or 1.45%.

How do I calculate DC voltage drop?

The same way as single-phase: the current runs out and back, so use 2 × I × R × L ÷ 1,000. Low-voltage circuits feel it most. 10 A on 25 ft of 10 AWG copper at 12 V drops 0.62 V, which is 5.2%, so batteries and solar runs usually need heavier wire than the current alone suggests.

What causes voltage drop?

The wire's resistance. Drop goes up with longer runs, thinner wire and more current. Aluminum resists about 1.6 times as much as copper of the same size, so it drops more.

Does this tell me what wire size I need?

Only for voltage drop. The wire also has to be rated for the current (NEC Table 310.16) and matched to the breaker, which often calls for a larger size. A wire size calculator is coming soon; until then, have a licensed electrician confirm the size.